That's a Nema 6-50
Your dryer will need a 30A receptacle, not the 50A you have. Also, you'll be short a crucial wire unless your dryer is old enough to only need 2+ground (you currently have two hots going to a double-pole 50A breaker, and a ground - new dryer will likely need 2 hots, a neutral, and a ground, on a 30a breaker). In other words, you may have to have new wire pulled anyway. Sorry.
Recommend: have electrician look and see about re-pulling the circuit with new Romex, 10/3. Dont just rig a cord unless you at LEAST swap the breaker, too. The wire can be upsized, the breaker and device cannot. If you've got basement access there, it could be a pretty quick job.
Source: am electrician
Who tf downvoted me, im the only actual electrician in this thread, ON THE ELECTRICIAN PAGE. I'm licensed and self-employed, which I'll happily verify with mods. Absurd.